FB pixel

Transformers as Two-Port Devices

Section 8.5 explains the principle of operation of the ideal transformer. The relationship governing the terminal voltages

and

was found to be

(8.6.1)

where

and

are the number of turns in the associated coils and

is either

or

depending on the relative orientation of the windings; i.e., whether the reference direction of the associated fluxes is the same or opposite, respectively.

We shall now consider ratios of current and impedance in ideal transformers, using the two-port model shown in Figure 8.6.1. By virtue of the reference current directions and polarities chosen in this figure, the power delivered by the source

is

, and the power absorbed by the load

is

. Assuming the transformer windings have no resistance, and assuming the magnetic flux is perfectly contained within the core, the power absorbed by the load must equal the power provided by the source; i.e.,

. Thus, we have1

We can develop an impedance relationship for ideal transformers as follows. Let

be the input impedance of the transformer; that is, the impedance looking into port 1 from the source. Thus, we have

In Figure 8.6.1,

is the the output impedance of port 2; that is, the impedance looking out port 2 into the load. Therefore,

(once again the minus sign is a result of our choice of sign conventions in Figure 8.6.1). Substitution of this result into the above equation yields

(8.6.3)

and therefore

(8.6.4)

Thus, we have demonstrated that a transformer scales impedance in proportion to the square of the turns ratio

. Remarkably, the impedance transformation depends only on the turns ratio, and is independent of the relative direction of the windings (

).

The relationships developed above should be viewed as AC expressions, and are not normally valid at DC. This is because transformers exhibit a fundamental limitation in their low-frequency performance. To see this, first recall Faraday’s Law:

(8.6.5)

If the magnetic flux

is not time-varying, then there is no induced electric potential, and subsequently no linking of the signals associated with the coils. At very low but non-zero frequencies, we encounter another problem that gets in the way – magnetic saturation. To see this, note we can obtain an expression for

from Faraday’s Law by integrating with respect to time, yielding

(8.8.6)

where

is some earlier time at which we know the value of

. Let us assume that

is sinusoidally-varying. Then the peak value of

after

depends on the frequency of

. If the frequency of

is very low, then

can become very large. Since the associated cross-sectional areas of the coils are presumably constant, this means that the magnetic field becomes very large. The problem with that is that most practical high-permeability materials suitable for use as transformer cores exhibit magnetic saturation; that is, the rate at which the magnetic field is able to increase decreases with increasing magnetic field magnitude (see Section 7.16). The result of all this is that a transformer may work fine at (say) 1 MHz, but at (say) 1 Hz the transformer may exhibit an apparent loss associated with this saturation. Thus, practical transformers exhibit highpass frequency response.

It should be noted that the highpass behavior of practical transistors can be useful. For example, a transformer can be used to isolate an undesired DC offset and/or low-frequency noise in the circuit attached to one coil from the circuit attached to the other coil.

The DC-isolating behavior of a transformer also allows the transformer to be used as a balun, as illustrated in Figure 8.6.2. A balun is a two-port device that transforms a single-ended (“unbalanced”) signal – that is, one having an explicit connection to a datum (e.g., ground) – into a differential (“balanced”) signal, for which there is no explicit connection to a datum. Differential signals have many benefits in circuit design, whereas inputs and outputs to devices must often be in single-ended form. Thus, a common use of transformers is to effect the conversion between single-ended and differential circuits. Although a transformer is certainly not the only device that can be used as a balun, it has one very big advantage, namely bandwidth.

Footnotes

  • 1

    The minus signs in this equation are a result of the referencepolarity and directions indicated in Figure 8.6.1. These are more-or-less standard in electrical two-port theory (see “Additional Reading”at the end of this section), but are certainly not the only reason-able choice. If you see these expressions without the minus signs,it probably means that a different combination of reference directions/polarities is in effect.

Additional Reading

 

Ellingson, Steven W. (2018) Electromagnetics, Vol. 1. Blacksburg, VA: VT Publishing. https://doi.org/10.21061/electromagnetics-vol-1 CC BY-SA 4.0

 
Use left and right arrow keys to change pagesUse left and right arrow keys to change pages.
Swipe left and right to change pages.\Swipe left and right to change pages.
Make Bread with our CircuitBread Toaster!

Get the latest tools and tutorials, fresh from the toaster.

What are you looking for?