Copper Wire Ampacity Table
Ampacities of copper wire: below
Ampacities of copper wire, in free air at 30o C:
INSULATION TYPE: | |||
---|---|---|---|
RUW, T | THW, THWN | FEP, FEPB | |
TW | RUH | THHN, XHHW | |
Size | Current Rating | Current Rating | Current Rating |
AWG | @ 60 degrees C | @ 75 degrees C | @ 90 degrees C |
20 | *9 | *12.5 | |
18 | *13 | 18 | |
16 | *18 | 24 | |
14 | 25 | 30 | 35 |
12 | 30 | 35 | 40 |
10 | 40 | 50 | 55 |
8 | 60 | 70 | 80 |
6 | 80 | 95 | 105 |
4 | 105 | 125 | 140 |
2 | 140 | 170 | 190 |
1 | 165 | 195 | 220 |
1/0 | 195 | 230 | 260 |
2/0 | 225 | 265 | 300 |
3/0 | 260 | 310 | 350 |
4/0 | 300 | 360 | 405 |
* = estimated values; normally, these small wire sizes are not manufactured with these insulation types, above.